Monarch NICE3000new Err35 — Well Learning Data Abnormal: Full Sub-Code Fix Guide

Err35 appears during commissioning or normal run of the NICE3000new when stored well (shaft) learning data is missing or inconsistent. The sub-code tells you exactly what went wrong during learning.

Important: Not Every Err35 Is a Real Fault

During slow-car commissioning, no well learning has been done yet, so Err35 with sub-code 103 appears at every power-up. This is normal — simply reset with the operator keypad. It does not affect slow-car commissioning.

Sub-Code Reference and Fixes

  • 101: current floor is not the lowest at learning start — check the next deceleration limit is active and F4-01 is the lowest floor
  • 102: inspection switch opened during learning — check whether the elevator is in inspection mode
  • 103, 104, 113, 114: no valid well learning — repeat well learning
  • 105: run direction inconsistent with pulse direction — confirm pulse change matches F4-03 (up = increase); if not, adjust with F2-10
  • 106, 107, 109: abnormal vane pulse length — check leveling sensor NO/NC setting and vane installation; check for strong-power interference
  • 108, 110: leveling signal unchanged over 45 s — check sensor wiring; if floor heights are large, increase learning speed F3-11
  • 111, 115: stored floor height below 50 cm — enable the short-floor function if a floor is genuinely short; otherwise check that floor’s vane/sensor/wiring
  • 112: learning finished but not at highest floor — maximum floor F6-00 set too small

Still stuck on this fault? Our engineers repair Monarch NICE3000 systems every day. Message us on WhatsApp (+86 139 8566 2489) — send a photo of your board or the fault display, and we will identify the part and guide you through the fix. Every board we sell is 100% run-tested with a 12-month warranty, MOQ 1 piece, and free remote parameter-setup support until your elevator runs.

Browse all codes in our free NICE3000 fault code library.