Err19 on a Monarch NICE3000new integrated controller means motor auto-tuning failed to identify parameters. It is a fault we handle regularly on NICE3000new systems overseas, and in most cases it comes from sub-code 1 rather than a failed main board.
Possible Causes
- Sub-code 1: stator resistance identification failed; Sub-code 5, 6: magnetic-pole position identification failed; Sub-code 8: reserved; Sub-code 11: angle save failed after angle-free tuning; Sub-code 101, 102: motor tuning timeout
Step-by-Step Troubleshooting
- 1. Sub-codes 1, 5, 6: check motor leads and output contactor for phase loss
- 2. Sub-code 11: motor moved too little before power-off after angle-free tuning — repeat angle-free tuning and let the motor run more than 3 revolutions continuously
- 3. Sub-code 101: PM loaded-tuning timeout — check encoder wiring or replace the PG card and re-tune
- 4. Sub-code 102: keypad-mode tuning timeout — check encoder wiring or replace the PG card and re-tune
Pro Tip From the Field
For angle-free tuning, let the motor run more than 3 revolutions before power-off, or Err19 sub-code 11 will repeat.
Still stuck on this fault? Our engineers repair and supply Monarch NICE3000 systems every day. Message us on WhatsApp (+86 139 8566 2489) — send a photo of your board or the fault display, and we will identify the part and guide you through the fix. Every board and part we ship is 100% run-tested before dispatch, with a 12-month warranty.