Err38 on a Monarch NICE3000new integrated controller means the encoder pulse behaviour was inconsistent with motion. It is a fault we handle regularly on NICE3000new systems overseas, and in most cases it comes from sub-code 101 rather than a failed main board.
Possible Causes
- Sub-code 101: no change in F4-03 pulses beyond the F1-13 threshold; 102: pulses increase while the motor runs down; 103: pulses decrease while the motor runs up; 104: open-loop run set in distance mode; 105: up-limit active while running up; 106: down-limit active while running up; 107: up-limit active while running down; 108: down-limit active while running down
Step-by-Step Troubleshooting
- 1. Sub-code 101: a. verify encoder settings and wiring b. verify the brake operates correctly
- 2. Sub-codes 102–103: a. verify encoder settings and wiring b. check system ground to signal ground bonding c. verify motor U/V/W phase sequence
- 3. Sub-code 104: set closed-loop run in distance mode (F0-00 = 1)
- 4. Sub-codes 105–106: check the limit switch wiring
- 5. Sub-codes 107–108: check the limit switch wiring
Pro Tip From the Field
For Err38, verify encoder settings/wiring, ground bonding, and motor phase sequence; set closed-loop run in distance mode (F0-00=1).
Still stuck on this fault? Our engineers repair and supply Monarch NICE3000 systems every day. Message us on WhatsApp (+86 139 8566 2489) — send a photo of your board or the fault display, and we will identify the part and guide you through the fix. Every board and part we ship is 100% run-tested before dispatch, with a 12-month warranty.