Err36 on a Monarch NICE3000new integrated controller means the run contactor feedback disagrees with the actual output. It is a fault we handle regularly on NICE3000new systems overseas, and in most cases it comes from sub-code 101 rather than a failed main board.
Possible Causes
- Sub-code 101: no output but feedback active; 102: output present but feedback inactive; 103: induction motor output current too small (≤0.1 A) from acceleration to constant-speed; 104: duplicated feedback contacts disagree; 105: run contactor feedback active before re-leveling start
Step-by-Step Troubleshooting
- 1. Sub-codes 101, 102, 104, 105: a. check the contactor feedback contacts b. verify feedback signal type (NO/NC)
- 2. Sub-code 103: check the controller U/V/W output wiring; check the run contactor coil control circuit
Pro Tip From the Field
Check the run-contactor feedback contacts and NO/NC setting; a welded or stuck contactor is common.
Still stuck on this fault? Our engineers repair and supply Monarch NICE3000 systems every day. Message us on WhatsApp (+86 139 8566 2489) — send a photo of your board or the fault display, and we will identify the part and guide you through the fix. Every board and part we ship is 100% run-tested before dispatch, with a 12-month warranty.