Monarch NICE3000new Err05 / Err06 / Err07 — Overvoltage Faults: Causes and Fixes

Err05 (overvoltage during acceleration), Err06 (during deceleration) and Err07 (at constant speed) share the same root causes on the Monarch NICE3000new system: the DC bus voltage rises above the protection threshold because braking energy cannot be discharged.

Possible Causes

  • Input supply voltage too high
  • Braking resistor value too large, or braking unit fault
  • Acceleration rate too high

Step-by-Step Troubleshooting

  • 1. Measure the input voltage. On a 380 V supply, the DC bus should read about 540–580 V.
  • 2. Check the braking resistor circuit. If bus voltage rises too fast during run, the resistor is not working or is mis-sized: inspect resistor wiring for damage or ground fault, re-confirm the resistance against the recommended table, and if a braking unit is fitted check for abnormal operation.
  • 3. Curve tuning. If resistance is normal and overvoltage occurs when speed reaches target, reduce F2-01/F2-04 to lower curve tracking error.
  • 4. Check acceleration/deceleration settings are not set too aggressively.

Pro Tip From the Field

A burnt braking resistor is one of the most frequent root causes of Err05/06/07 in hot climates. Always check the resistor before replacing the main board.


Still stuck on this fault? Our engineers repair Monarch NICE3000 systems every day. Message us on WhatsApp (+86 139 8566 2489) — send a photo of your board or the fault display, and we will identify the part and guide you through the fix. Every board we sell is 100% run-tested with a 12-month warranty, MOQ 1 piece, and free remote parameter-setup support until your elevator runs.

Browse all codes in our free NICE3000 fault code library.


评论

发表回复

您的邮箱地址不会被公开。 必填项已用 * 标注